The fire safety rules in BS 7671 are written to prevent catastrophic outcomes. This guide focuses on the undesirable consequences of non-compliance and details the specific IET Wiring Regulations put in place to eliminate that risk.
Electrical installation design guide PDF
Consequence 1: Fire Initiation from an Electrical Fault
The Risk: A fault, such as a loose terminal or damaged cable, causes overheating or arcing, which ignites nearby dust or building materials.
-
BS 7671 Prevention:
-
The AFDD Mandate (Regulation 421.1.7): To prevent low-energy arc faults from starting a fire, Arc Fault Detection Devices (AFDDs) must be installed on certain final circuits in high-risk residential buildings. This is because traditional breakers often won't trip on the small current draw of an arc fault.
-
Overload Protection (Chapter 43): Correct design ensures that the cable's current-carrying capacity ($\mathbf{I_z}$) is greater than the protection device's rating ($\mathbf{I_n}$). This guarantees the breaker trips long before the cable heats up enough to cause thermal damage or ignition.
-
Proper Termination: All connections must be secure and tightened to the correct torque settings to eliminate resistance that causes localised heat build-up.
-
Consequence 2: Fire Spreads Beyond the Point of Origin
The Risk: A fire starts in one area (like the consumer unit or a cable penetration) and uses the electrical installation to spread to other parts of the building, defeating the structural fire compartmentation.
-
BS 7671 Prevention:
-
Containment at the Board (Regulation 421.1.201): In dwellings, consumer units must be housed in a non-combustible enclosure (e.g., metal). This contains the fire at its most common source, preventing flames from escaping the unit.
-
Sealing Penetrations (Regulation 527.2): Where cables or containment pass through a fire-rated wall or floor, the electrician must restore the fire resistance of that element using approved fire-stopping materials. This ensures the fire cannot use the wiring pathway to move between compartments.
-
Smoke and Gas Control (Regulation 527.1.1): In high-occupancy or complex buildings, materials must be selected to minimise fire spread. Using Low Smoke Halogen Free (LSZH) cables prevents the rapid spread of toxic, corrosive smoke that can make evacuation impossible.
-
Consequence 3: Hinderance to Evacuation and Injury to Firefighters
The Risk: Cables fall from the ceiling onto escape routes, creating entanglement hazards for people trying to evacuate and emergency services personnel trying to enter.
-
BS 7671 Prevention:
-
The Anti-Collapse Rule (Regulation 521.10.202): All wiring systems throughout the building must be supported by metal or non-combustible fixings. Plastic ties and clips are not sufficient as they melt quickly, leading to the collapse of the wiring system.
-
Sterile Protected Routes (Chapter 422): In designated protected escape routes (stairwells, fire lobbies), the installation of non-essential electrical equipment is severely restricted. Only emergency safety systems and essential lighting/cleaning sockets are permitted, and these must use fire-resistant cable systems to remain operational during the fire. This keeps the escape path clear and functional.
-